Skip to main content
Menu
Microsoft Azure

Multiple services – Power/cooling issues in West US 2

DWN-d90db20934Microsoft AzureStarted Impact not stated

Impact
Impact not stated
Status
Resolved after 22h 6m
Affected
us

What's happening

Watch our 'Azure Incident Retrospective' video about this incident: https://aka.ms/air/GHRP-84G What happened? Between 04:24 UTC on 29 May and 02:30 UTC on 30 May 2026, customers with resources in the West US 2 region may have experienced failures when attempting to access or manage some Azure services in the region. Impact included connectivity failures, resource unavailability, and service management failures. The issue was triggered by a severe thunderstorm that caused utility power disturbances affecting multiple datacenter facilities serving the region. These disturbances led to some cooling systems entering a protective mode to preserve equipment integrity. This caused elevated temperatures which triggered proactive shutdowns of infrastructure affecting compute, networking, and storage systems across two different availability zones in the region (physical AZ-01 and AZ-03). After cooling systems stabilized, storage services - and the networking on which they depend - required extensive manual recovery actions, which contributed to the total duration of customer impact. The following services were among those affected: Application Insights, Azure App Service, Azure Backup, Azure Cache for Redis, Azure Container Registry, Azure Cosmos DB, Azure Databricks, Azure Data Explorer, Azure Data Factory, Azure Functions, Azure IoT Hub, Azure Kubernetes Service, Azure Monitor, Azure NetApp Files, Azure Resource Manager, Azure Site Recovery, Azure SQL Database, Azure Storage, Azure Synapse Analytics, Azure Virtual Machines, Log Analytics, Service Bus, and Virtual Machine Scale Sets. What went wrong and why? A severe thunderstorm produced lightning strikes, resulting in utility power disturbances across multiple datacenter facilities serving the West US 2 region. These disturbances affected a wide enough geographic area that a subset of datacenters within two Availability Zones experienced impact. While this event was not a complete utility power interruption, these datacenters experienced multiple voltage sag/swell events, meaning utility power remained present but was unstable. The region consists of datacenters built at different times with varying infrastructure designs, including differences in cooling control systems and power protection mechanisms. Some datacenters transferred to generator power, while others did not transfer, as the utility power source remained available even as voltage fluctuated. Independently of whether each datacenter transferred to backup power, a subset of components within the mechanical cooling systems - across multiple datacenters - detected abnormal electrical conditions and, by design, entered a 'lockout' protective state. This reduced cooling capability and prevented parts of the cooling system from automatically returning to normal operation after the power disturbance. As temperatures rose beyond safe operating thresholds, a subset of cloud infrastructure automatically shut down to prevent physical damage and preserve data integrity. Impacted cooling systems required manual intervention and troubleshooting, including multiple restart attempts before stable cooling capacity could be reestablished. Additionally, we had to identify which devices required manual recovery and which were expected to self-recover. Impacted Storage scale units required additional validation. These factors contributed to the extended recovery time for services dependent on storage, including telemetry processing systems. How did we respond? Recovery efforts began immediately, prioritizing cooling restoration, then network infrastructure, followed by compute and storage systems. Cooling was restored within approximately two hours of impact start. The majority of compute resources recovered within eight hours. Storage validation, which must be performed sequentially, extended over approximately 14 hours. Finally, telemetry services (Application Insights and Log Analytics) required an additional six hours bey

Microsoft Azure,

What to do

  1. Check whether you use Microsoft Azure in us. Check your stack.

    Drop a package.json, lockfile, Terraform or a list of domains at down.guide to see every provider you depend on.
  2. Confirm your retries, queues and scheduled jobs caught up after the 22h 6m it lasted.

    Anything that failed between 2026-05-29 04:24 UTC and 2026-05-30 02:30 UTC may need a replay.
  3. Subscribe to Microsoft Azure's feed to hear about the next one first. RSS feed.

    https://down.guide/feed?provider=azure works in Slack (/feed subscribe), Discord feed bots and any RSS reader.

Updates from Microsoft Azure 1

  1. Postmortem

    Watch our 'Azure Incident Retrospective' video about this incident: https://aka.ms/air/GHRP-84G What happened? Between 04:24 UTC on 29 May and 02:30 UTC on 30 May 2026, customers with resources in the West US 2 region may have experienced failures when attempting to access or manage some Azure services in the region. Impact included connectivity failures, resource unavailability, and service management failures. The issue was triggered by a severe thunderstorm that caused utility power disturbances affecting multiple datacenter facilities serving the region. These disturbances led to some cooling systems entering a protective mode to preserve equipment integrity. This caused elevated temperatures which triggered proactive shutdowns of infrastructure affecting compute, networking, and storage systems across two different availability zones in the region (physical AZ-01 and AZ-03). After cooling systems stabilized, storage services - and the networking on which they depend - required extensive manual recovery actions, which contributed to the total duration of customer impact. The following services were among those affected: Application Insights, Azure App Service, Azure Backup, Azure Cache for Redis, Azure Container Registry, Azure Cosmos DB, Azure Databricks, Azure Data Explorer, Azure Data Factory, Azure Functions, Azure IoT Hub, Azure Kubernetes Service, Azure Monitor, Azure NetApp Files, Azure Resource Manager, Azure Site Recovery, Azure SQL Database, Azure Storage, Azure Synapse Analytics, Azure Virtual Machines, Log Analytics, Service Bus, and Virtual Machine Scale Sets. What went wrong and why? A severe thunderstorm produced lightning strikes, resulting in utility power disturbances across multiple datacenter facilities serving the West US 2 region. These disturbances affected a wide enough geographic area that a subset of datacenters within two Availability Zones experienced impact. While this event was not a complete utility power interruption, these datacenters experienced multiple voltage sag/swell events, meaning utility power remained present but was unstable. The region consists of datacenters built at different times with varying infrastructure designs, including differences in cooling control systems and power protection mechanisms. Some datacenters transferred to generator power, while others did not transfer, as the utility power source remained available even as voltage fluctuated. Independently of whether each datacenter transferred to backup power, a subset of components within the mechanical cooling systems - across multiple datacenters - detected abnormal electrical conditions and, by design, entered a 'lockout' protective state. This reduced cooling capability and prevented parts of the cooling system from automatically returning to normal operation after the power disturbance. As temperatures rose beyond safe operating thresholds, a subset of cloud infrastructure automatically shut down to prevent physical damage and preserve data integrity. Impacted cooling systems required manual intervention and troubleshooting, including multiple restart attempts before stable cooling capacity could be reestablished. Additionally, we had to identify which devices required manual recovery and which were expected to self-recover. Impacted Storage scale units required additional validation. These factors contributed to the extended recovery time for services dependent on storage, including telemetry processing systems. How did we respond? Recovery efforts began immediately, prioritizing cooling restoration, then network infrastructure, followed by compute and storage systems. Cooling was restored within approximately two hours of impact start. The majority of compute resources recovered within eight hours. Storage validation, which must be performed sequentially, extended over approximately 14 hours. Finally, telemetry services (Application Insights and Log Analytics) required an additional six hours bey

Reports count in aggregate; nothing about you is shown.

Questions about Multiple services – Power/cooling issues in West US 2

Is Microsoft Azure still down?

No, this incident was resolved 2026-05-30 02:30 UTC. For Microsoft Azure's live state, see https://down.guide/providers/azure.

How long did it last?

22h 6m, from 2026-05-29 04:24 UTC to 2026-05-30 02:30 UTC, by the times Microsoft Azure posted.

What was affected?

Microsoft Azure named in us.

What caused it?

Microsoft Azure hasn't published a root cause. If it does, it shows here.

Where does this come from?

Microsoft Azure's official status page, https://azure.status.microsoft/en-us/status, quoted verbatim. down.guide's own probes, reports and social counts are labeled as ours.

All Microsoft Azure incidents

No corrections so far. Something wrong on this page? Report an error or send us a note.